BV1 - Phase sequence relay
Application Supervision of phase loss, phase sequence and undervoltage in three-phase systems.
Function Relay BV1 measures amplitude and angle of three phase voltages. The angle of the phasors determine the phase sequence. Unbalance and phase loss are detected by the measurement of amplitude and angle. www.DataSheet4U.com The undervoltage trip setting is 70 % of Un fixed. The underfrequency element trips if the frequency falls below 45 Hz.
Technical data rated voltage Un: frequency range: hysteresis: power consumption: thermal load carrying capacity: returning time: minimum operating time:
110 V, 230 V, 400 V AC 45 - 66 Hz 2% Un 3 VA (4 VA BA1-400) continuously 1,3 x Un 700 ms 700 ms
Fig. 1: Front plate
Output relays: max.