• Part: SGX-4NH3-300
  • Description: Industrial Ammonia Sensor
  • Manufacturer: SGX
  • Size: 316.10 KB
Download SGX-4NH3-300 Datasheet PDF
SGX
SGX-4NH3-300
SGX-4NH3-300 Datasheet Industrial Ammonia (NH3) Sensor PERFORMANCE Output signal Typical Baseline Range (pure air) T90 Response Time Measurement Range Maximum Overload Linearity Repeatability Remended Load Resistor Resolution (Electronics dependent) 40 ± 15 n A / ppm ±2ppm NH3 equivalent < 75 seconds 0 - 300 ppm 500 ppm Linear ±10% 10 ohms 2 ppm SGX Europe Sp. Z o.o. Building 11 Ligocka St. 103, 40-568 Katowice, Poland T: +48 (0) 32 438 4778 E: sales.is@sgxsensortech. .sgxsensortech. OUTLINE All dimensions are in mm All tolerances are ±0.15mm OPERATING CONDITIONS Temperature Range -40°C to +50°C Pressure Range 800 to 1200 mbar Operating Humidity Range 15% to 90% RH LIFETIME Long Term Output Drift Remended Storage Temp Expected Operating Life < 20% per annum 0°C to 20°C > 24 months in air INTRINSIC SAFETY DATA Max at 2000ppm 0.3 m A Max o/c Voltage 1.3 V Max s/c Current <1.0 A © SGX Sensortech 2012-2020 DS-0306 SGX-4NH3-300, Issue 2, 26-Mar-2020, Page 1/3 CROSS -...