Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise and motor starting Sustained short circuit current of up to 300% of the rated current for up to 10 seconds Self-Ventilated and Drip-Proof Superior Voltage Waveform Digital, Solid State, Volts-per-Hertz Regulator No Load to Full Load Regulation Brushless Alternator with Brushless Pilot Exciter 4 Pole, Rotating Field 130°C Standby Temperature Rise 1 Bearing, Sealed Full Amortisseur Windings 125% Rotor Balancing 3-P.
The following content is an automatically extracted verbatim text
from the original manufacturer datasheet and is provided for reference purposes only.
View original datasheet text
A tognum Group Brand
Diesel Engine-Generator Set 40-JS6DT3
40 ekW / 60 Hz / Standby 208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model Temp Rise Connection
** UL2200 Offered
240V** 1 1.0 60 40 40 167 63 361CSL1601 130°C/27°C 12 LEAD ZIG-ZAG
208V** 3 0.8 60 40 50 139 105 361CSL1601 130°C/27°C 12 LEAD LOW WYE
240V** 3 0.8 60 40 50 120 105 361CSL1601 130°C/27°C 12 LEAD HI DELTA
480V** 3 0.8 60 40 50 60 140 361CSL1601 130°C/27°C 12 LEAD HI WYE
600V** 3 0.