Datasheet4U Logo Datasheet4U.com

SCM7B33 - Isolated Process Current/Voltage Input Modules

Download the SCM7B33 datasheet PDF. This datasheet also covers the SCM7B32 variant, as both devices belong to the same isolated process current/voltage input modules family and are provided as variant models within a single manufacturer datasheet.

Description

The SCM7B32 current input modules accept input signals in the 4-20mA or 0-20mA ranges from the field and provide a high-level output to the process control system (Figure 1).

Current to voltage conversion occurs internal to the module, which is factory calibrated to ensure the highest accuracy.

Features

  • Accepts Current or Voltage Input.
  • Provides High-Level Voltage Outputs.
  • 1500Vrms Transformer Isolation.
  • Accuracy, ±0.03% of Span Typical, ±0.1% Max.
  • ANSI/IEEE C37.90.1 Transient Protection.
  • Input Protected to 120Vrms Continuous.
  • Noise, 500µVp-p (5MHz), 300µVrms (100kHz).
  • 105dB CMRR.
  • Easy DIN Rail Mounting.
  • CSA C/US Certified.
  • CE and ATEX Compliant Figure 1: SCM7B32/33 Block Diagram 72 For inform.

📥 Download Datasheet

Note: The manufacturer provides a single datasheet file (SCM7B32-Dataforth.pdf) that lists specifications for multiple related part numbers.

Datasheet Details

Part number SCM7B33
Manufacturer Dataforth
File Size 223.67 KB
Description Isolated Process Current/Voltage Input Modules
Datasheet download datasheet SCM7B33 Datasheet

Full PDF Text Transcription

Click to expand full text
Isolated Process Control Signal Conditioning Products SCM7B SCM7B32/33 Isolated Process Current/V oltage Input Modules Description The SCM7B32 current input modules accept input signals in the 4-20mA or 0-20mA ranges from the field and provide a high-level output to the process control system (Figure 1). Current to voltage conversion occurs internal to the module, which is factory calibrated to ensure the highest accuracy. SCM7B33 voltage input modules accept input signals in the +1V to +5V or 0 to +5V ranges from the field and provide a high-level output to the process control system. As an alternative, the SCM7B33 can be used with an external 250Ω resistor (Dataforth SCM7BXR1 or equivalent), to accept input signals in the 4-20mA or 0-20mA ranges.
Published: |