Oil Drain Extension & S/O Valve Flexible Fuel Connector Battery Cables Vibration Isolation Pads Jacket Water Heater: -20° F Mainline Circuit Breaker UL2200 Listed Steel Sub-Base Radiator Duct Flange (OPU) Lube Oil & Antifreeze Operator’s and Owner’s Manual 2 Year/3000 Hour Warranty Factory Tested at 0.8 PF (3 PH)
Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise and motor starting Sustained short circuit current of up to 300% of the rated current for up to 10 seconds S.
The following content is an automatically extracted verbatim text
from the original manufacturer datasheet and is provided for reference purposes only.
View original datasheet text
A tognum Group Brand
Diesel Engine-Generator Set 500-XS6DT2 500 ekW 60 Hz Standby
/ /
208 - 600V
System Ratings
Standby
Voltage (L-L) Phase PF Hz kW kVA AMPS skVA@30% Voltage Dip Generator Model Temp Rise Connection
** UL2200 Offered
208V** 3 0.8 60 500 625 1735 1470 572RSL4029 130°C/27°C 12 LEAD HI DELTA
240V** 3 0.8 60 500 625 1504 1470 572RSL4029 130°C/27°C 12 LEAD HI WYE
480V** 3 0.8 60 500 625 752 1280 572RSL4027 130°C/27°C 12 LEAD HI WYE
600V** 3 0.