MTU Onsite Energy
MTU Onsite Energy


400-XC6DT3

DIESEL ENGINE-GENERATOR SET



No Preview Available !

400-XC6DT3 pdf
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET
400-XC6DT3
400 ekW / 60 Hz / Standby
340 ekW / 60 Hz / Prime
208 - 4160V
System Ratings
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1.0
60
400
400
1667
700
573RSL4035
130°C/27°C
12 LEAD ZIG-ZAG
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
wwwGTee.mDnepartRaatiSsoher eMeot4deUl*.c om
Connection
240V
1
1.0
60
340
340
1417
700
573RSL4035
105°C/40°C
12 LEAD ZIG-ZAG
208V**
3
0.8
60
400
500
1388
240V**
3
0.8
60
400
500
1203
820
433CSL6220
130°C/27°C
12 LEAD LOW WYE
820
433CSL6220
130°C/27°C
12 LEAD HI DELTA
208V
3
0.8
60
340
425
1180
240V
3
0.8
60
340
425
1022
820
433CSL6220
105°C/40°C
12 LEAD LOW WYE
820
433CSL6220
105°C/40°C
12 LEAD HI DELTA
480V**
3
0.8
60
400
500
601
600V**
3
0.8
60
400
500
481
1100
433CSL6220
130°C/27°C
12 LEAD HI WYE
1100
433PSL6248
125°C/40°C
4 LEAD WYE
480V
3
0.8
60
340
425
511
600V
3
0.8
60
340
425
409
1100
433CSL6220
105°C/40°C
12 LEAD HI WYE
1100
433PSL6248
105°C/40°C
4 LEAD WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
4160V
3
0.8
60
400
500
69
1100
573FSM4352
130°C/27°C
6 LEAD WYE
4160V
3
0.8
60
340
425
59
1100
573FSM4352
105°C/40°C
6 LEAD WYE



No Preview Available !

400-XC6DT3 pdf
2 / //  / 400-XC6DT3
Facts
//  EPA Tier 3 Certified
//  Engine-Generator Set Tested to ISO 8528-5 for
Transient Response
//  UL2200, CSA Listing Offered
//  Accepts Rated Load in One Step Per NFPA 110, Level 1
//  All engine-generator sets are prototype and factory tested
//  MTU Onsite Energy is a single source supplier
//  Global Product Support
//  2 Year Standard Warranty
//  Custom Design for Any Application
//  Series 60 (6063HV35) Diesel Engine
- 14.0 Liter Displacement
- Electronic Unit Pump Injection
- 4-Cycle
STANDARD EQUIPMENT
//  Complete Range of Accessories
//  Permanent Magnet Generator (PMG) - Optional
- Brushless, Rotating Field
- 300% Short Circuit Capability
- 2/3 Pitch Windings
//  Digital Control Panel(s)
- UL Recognized, , NFPA 110
- Complete System Metering
- LCD Display
//  Cooling System
- Integral Set-Mounted
- Engine Driven Fan
//  Engine
Air Cleaners
Oil Pump
Full Flow Oil Filter
Jacket Water Pump
Thermostat
Exhaust Manifold – Dry
Blower Fan & Fan Drive
Radiator - Unit Mounted
Electric Starting Motor - 24V
Governor – Electric Isochronous
Base - Formed Steel
SAE Flywheel & Bell Housing
Charging Alternator - 24V
Battery Box & Cables
Flexible Fuel Connectors
Flexible Exhaust Connection
EPA Certified Engine
//  Generator
NEMA MG1, IEEE and ANSI standards compliance for temperature rise
and motor starting
Sustained short circuit current of up to 300% of the rated current for up
tow1w0wse.DcoantdasSheet4U.com
Self-Ventilated and Drip-Proof
Superior Voltage Waveform
Digital, Solid State, Volts-per-Hertz Regulator
No Load to Full Load Regulation
Brushless Alternator with Brushless Pilot Exciter
4 Pole, Rotating Field
130°C Standby Temperature Rise
1 Bearing, Sealed
Flexible Coupling
Full Amortisseur Windings
125% Rotor Balancing
3-Phase Voltage Sensing
±1% Voltage Regulation
100% of Rated Load - One Step
3% Maximum Harmonic Content
//  Digital Control Panel(s)
Digital Metering
Engine Parameters
Generator Protection Functions
Engine Protection
SAE J1939 Engine ECU Communications
Windows-Based Software
Multilingual Capability
Remote Communications to our RDP-110 Remote Annunciator
16 Programmable Contact Inputs
7 Contact Outputs
UL Recognized,
, CE Approved
Event Recording
IP 54 Front Panel Rating with Integrated Gasket
NFPA110 Level Compatible



Part Number 400-XC6DT3
Description DIESEL ENGINE-GENERATOR SET
Maker MTU Onsite Energy - MTU Onsite Energy
Total Page 4 Pages
PDF Download
400-XC6DT3 pdf
Download PDF File
400-XC6DT3 pdf
View for Mobile




Featured Datasheets

Part Number Description Manufacturers PDF
400-XC6DT3 DIESEL ENGINE-GENERATOR SET 400-XC6DT3
MTU Onsite Energy
PDF


Part Number Start With

0  1  2  3  4  5  6  7  8  9  A  B  C  D  E  F  G  H  I  J  K  L  M  N  O  P  Q  R  S  T  U  V  W  X  Y  Z

site map

webmaste! click here

contact us

Buy Components