Digital Temperature Controllers
Compact and Intelligent Temperature Controllers
Depth of only 78 mm. Various temperature inputs: thermocouple, platinum resistance thermometer, non-contact temperature sensor, and analog inputs. Auto-tuning and self-tuning available. Auto-tuning is possible even while self-tuning is being executed. Heating or heating/cooling control is available. Event input allows multiple SP selection and run/stop function. Water-resistant construction (NEMA4X: equivalent to IP66). Conforms to UL, CSA, and IEC safety standards as well as CE marking.
E5EN
48(W) x 96(H) x 78(D) mm
Ordering Information
E5EN Standard Models
Size Power supply voltage No. of alarm points Output Heater burnout alarm Thermocouple model Platinum resistance thermometer model E5EN-R3MP-500 E5EN-R3HMP-500 E5EN-Q3MP-500 E5EN-Q3HMP-500 E5EN-C3MP-500 E5EN-R3MP-500 E5EN-R3HMP-500 E5EN-Q3MP-500 E5EN-Q3HMP-500 E5EN-C3MP-500
1/8 DIN /8 48(W) x 96(H) x 78(D) mm
100 to 240 VAC 00 o 0 C
3
Relay e ay Voltage output (for driving SSR) Current
No Yes No Yes No No Yes No Yes No
E5EN-R3MTC-500 E5EN-R3HMTC-500 E5EN-Q3MTC-500 E5EN-Q3HMTC-500 E5EN-C3MTC-500 E5EN-R3MTC-500 E5EN-R3HMTC-500 E5EN-Q3MTC-500 E5EN-Q3HMTC-500 E5EN-C3MTC-500
24 VAC/VDC C/ C
3
Relay e ay Voltage output (for driving SSR) Current
Note:
1. A Current Transformer (CT) is not provided with the Unit. Be sure to order one when ordering the E5EN. 2. When the heating and cooling function is used, the number of alarm outputs will be reduced to 2. 3. When the heating and cooling function or the heater burnout alarm is used, one of the alarm outputs will be disabled for each function used. 4. Specify the power supply specifications when ordering.
E5EN Option Units
The E5EN provides communication or event input functionality when mounted with one of the following Option Units. Name Co Communication u ca o Unit U it Event Input Unit Model E53-AK01 E53-AK03 E53-AKB Function RS-232C communication RS-485 communication Event input
Current Transformer (Sold Separately)
Model Hole diameter E54-CT1 5.8 dia. E54-CT3 12.0 dia.
Terminal Cover (Sold Separately)
Model E53-COV03
10
E5EN www.DataSheet4U.com Input Ranges
Platinum Resistance Thermometer Input/Thermocouple Input
Platinum resistance thermometer input Input type Name 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 –100 –200 Platinum resistance thermometer Pt100 JPt100
E5EN
Temperature rangentlp
850
500.0
500.0
100.0 0.0 –200 –199.9 –199.9
100.0 0.0
Set value
0
1
2
3
4
Thermocouple input Input type Name 1800 1700 1600 1500 1400 1300 1200 1100 1000 900 800 700 600 500 400 300 200 100 0 –100 –200 K J T Thermocouple E L U N R
1700
ES1A Non-contact Temperature Sensor S
1700
Analog input 0 to 50 mV Usable in the following ranges by scaling: –1999 to 9999 or –199.9 to 999.9
B
1800
K10 to 70°C
K60 to 120°C
K115 to K160 to 165°C 260°C
1300
1300
Temperature rangentlp
850
850
600 500.0 400.0 400 400 260 120 70 100 –20.0 –100 –200 –200 –20.0 0 –100 –200 –200 0 0 0 0 0 0 165
Set value
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Applicable standards by input type are as follows: K, J, T, E, N, R, S, B: JIS C1602-1995 L: Fe-CuNi, DIN 43710-1985 U: Cu-CuNi, DIN 43710-1985 JPt100: JIS C1604-1989, JIS C1606-1989 Pt100: JIS C1604-1997, IEC751 Shaded ranges indicate default settings.
11
E5EN www.DataSheet4U.com
E5EN
Specifications
Ratings
Supply voltage Operating voltage range Power consumption Sensor input 100 to 240 VAC, 50/60 Hz 85% to 110% of rated supply voltage 9 VA Thermocouple: K, J, T, E, L, U, N, R, S, B Platinum resistance thermometer: Non-contact temperature sensor: Voltage input: 0 to 50 mV Control output Relay output Voltage output Current output Alarm output Control method Setting method Indication method Other functions Ambient temperature Ambient humidity Storage temperature SPST-NO, 250 VAC, 5 A (resistive load), electrical life: 100,000 operations 12 VDC (PNP), max. load current: 40 mA, with short-circuit protection circuit 4 to 20 mA DC, load: 600 Ω max., resolution: approx. 2,600 SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations 2-PID or ON/OFF control Digital setting using front panel keys 7-segment digital display and single-lighting indicator Character height: PV: 14.0 mm; SV: 9.5 mm According to Controller model –10 to 55_C (with no condensation or icing) 25% to 85% –25 to 65_C (with no condensation or icing) Pt100, JPt100 K10 to 70_C, K60 to 120_C, K115 to 165_C, K160 to 260_C 5 VA/4 W 24 VAC, 50/60 Hz/24 VDC
Characteristics
Indication accuracy Thermocouple: (±0.5% of indicated value or ±1_C, whichever greater) ±1 digit max. (see note ) Platinum resistance thermometer: (±0.5% of indicated value or ±1_C, whichever greater) ±1 digit max. Analog input: ±0.5% FS±1 digit max. CT input: ±5% FS±1 digit max. Hysteresis Proportional band (P) Integral time (I) Derivative time (D) Control period Manual reset value Alarm setting range Sampling period Insulation resistance Dielectric strength Vibration resistance Shock resistance Weight Protective structure Memory protection EMC 0.1 to 999.9 EU (in units of 0.1 EU) 0.1 to 999.9 EU (in units of 0.1 EU) 0 to 3999 s (in units of 1 s) 0 to 3999 s (in units of 1 s) 1 to 99 s (in units of 1 s) 0.0% to 100.0% (in units of 0.1%) -1999 to 9999 (decimal point position depends on input type) 500 ms 20 MΩ min. (at 500 VDC) 2000 VAC, 50 or 60 Hz for 1min (between different charging terminals) 10 to 55 Hz, 10 m/s2 for 2 hours each in X, Y and Z directions 300 m/s2, 3 times each in 3 axes, 6 directions (relay: 100 m/s2) Approx. 260 g Mounting bracket: Approx. 100 g Front panel: NEMA4X for indoor use (equivalent to IP66), rear case: IP20, terminals: IP00 EEPROM (non-volatile memory) (number of writes: 100,000) Emission Enclosure: Emission AC Mains: Immunity ESD: Immunity RF-interference: Immunity Conducted Disturbance: Immunity Burst: Approved standards EN55011 Group 1 class A EN55011 Group 1 class A EN61000-4-2: 4 kV contact discharge (level 2) 8 kV air discharge (level 3) ENV50140: 10 V/m (amplitude modulated, 80 MHz to 1 GHz) (level 3) 10 V/m (pulse modulated, 900 MHz) ENV50141: 10 V (0.15 to 80 MHz) (level 3) EN61000-4-4: 2 kV power-line (level 3) 2 kV I/O signal-line (level 4)
UL3121-1, CSA22.2 No. 14, E.B.1402C Conforms to EN50081-2, EN50082-2, EN61010-1 (IEC61010-1) Conforms to VDE0106/part 100 (Finger Protection), when the terminal cover is mounted.
Note:
The indication of K thermocouples in the -200 to 1300°C range, and T and N thermocouples at a temperature of -100°C or less, and U and L thermocouples at any temperature is ±2°C±1 digit maximum. The indication of B thermocouples at a temperature of 400°C or less is unrestricted. The indication of R and S thermocouples at a temperature of 200°C or less is ±3°C±1 digit maximum.
12
E5EN www.DataSheet4U.com Communications Specifications
Transmission path connection Communications method (see note 1) Synchronization method Baud rate Transmission code Data bit length (see note 2) Stop bit length (see note 2) Error detection Multiple points RS-485 (two-wire, half duplex)/RS-232C Start-stop synchronization 1,200/2,400/4,800/9,600/19,200 bps ASCII 7 or 8 bits 1 or 2 bits Vertical parity (none, even, odd) Frame check sequence (FCS): with SYSMAC WAY Block check character (BCC): with CompoWay/F Not available RS-485/RS-232C Not available 40 bytes
E5EN
Flow control Interface (see note 1) Retry function Communications buffer Note:
1. RS-232C communications are only supported for the E5AN and E5EN models. 2. The baud rate, data bit length, stop bit length, or vertical parity can be individually set using the communications setting level.
Current Transformer (Sold Separately) Ratings
Dielectric strength Vibration resistance Weight Accessories (E54-CT3 only) 1,000 VAC (1 min) 50 Hz 98 m/s2 E54-CT1: Approx. 11.5 g E54-CT3: Approx. 50 g Armature (2) Plug (2)
Heater Burnout Alarm Specifications
Max. heater current Input current readout accuracy Heater burnout alarm setting range Min. detection ON time Note: Single-phase AC: 50 A (see note 1) ±5%FS±1 digit max. 0.0 to 50.0 A (0.1 A units) (see note 2) 190 ms (see note 3)
1. When heater burnout is detected on a 3-phase heater, use the K2CU-FjjA-jGS (with gate input terminal). 2. When the set value is “00 A,” the heater burnout alarm will always be OFF. When the set value is “50.0 A,” the heater burnout alarm will always be ON. 3. When the control output ON time is less than 190 ms, heater burnout detection and heater current measurement will not be carried out.
13
E5EN www.DataSheet4U.com
E5EN
Nomenclature
Operation indicators
Temperature unit
No.1 display
No.2 display Operation indicators
Mode key
Up key
Level key Down key
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Panel Cutouts
Mounted Separately Group Mounted (48number of units -2.5) +1.0
0
120 min.
• Recommended panel thickness is 1 to 8 mm. • Group mounting is not possible in the vertical
direction. (Maintain the specified mounting space between Controllers when they are group mounted.)To mount the E5EN so that it is waterproof, apply the waterproof packing to the E5EN.
Group mounting does not allow waterproofing.
• To mount the E5EN so that it is waterproof, apply
the waterproof packing to the E5EN.
• When two or more E5ENs are mounted, make
sure that the surrounding temperature does not exceed the allowable operating temperature specified in the specifications.
14
E5EN www.DataSheet4U.com
Current Transformer (Sold Separately)
E54-CT1 E54-CT3
E5EN
Terminal Cover (Sold Separately)
E53-COV03
48
93.3
2.36 dia. 5.8 dia. 12 dia. 22
40 x 40
8.9
Two, 3.5 dia. Two, M3 (depth: 4)
Wiring Terminals
• The voltage output (control output) is not electrically insulated
from the in |